Modern electrical grids are undergoing profound physical transformations as massive volumes of distributed renewable generation connect to local distribution infrastructure, turning traditionally passive terminal networks into active networks governed by complex bidirectional power flows. Under these evolving conditions, operational fluctuations originating within distribution systems are no longer safely confined to local circuits; instead, volatile generation patterns propagate upstream across transmission-distribution interfaces, creating acute challenges for wide-area frequency support, tie-line balance, and voltage stability. To address the resulting operational uncertainties, researchers have formulated a comprehensive risk quantification framework that unites subjective expert judgment, data-driven objective analysis, and cloud model theory. Published in Sustainable Energy Research, the investigation demonstrates how coupling the Order Relation Analysis technique and the Criteria Importance Through Intercriteria Correlation approach with a three-parameter cloud model provides power grid dispatchers with an exact, mathematically grounded methodology for evaluating operational security across interconnected network layers under deep renewable penetration.
Traditional operational risk models frequently struggle when applied to modern coordinated transmission and distribution systems because existing analytical practices predominantly evaluate network layers in isolation. When transmission networks and distribution circuits are evaluated through separate, decoupled frameworks, operators fail to capture the multidimensional physical coupling and dynamic hazard evolution that characterize integrated grid architectures. Furthermore, established risk assessment routines often depend upon deterministic boundaries with fixed security thresholds, overlooking the pervasive randomness and cognitive ambiguity inherent in real-time power flow measurements. While optimization-based scheduling methods can compute dispatch decisions under predefined uncertainty distributions, they lack the granular, indicator-based diagnostic capability required to identify emerging vulnerabilities across competing operational dimensions. The researchers sought to overcome these analytical constraints by developing a unified risk evaluation framework capable of seamlessly converting qualitative semantics and quantitative telemetry into actionable operational intelligence.
To establish an indicator index that accurately mirrors the physical reality of grid dispatch, the research team designed a structured two-stage screening process initiated through an extensive technical survey across a regional power grid utility in China. The survey gathered feedback from 108 validated operational experts representing diverse engineering domains, including power dispatching and operation, transmission and substation maintenance, distribution system operation, renewable energy integration, and long-term grid planning. More than sixty percent of participating professionals possessed over a decade of hands-on power system experience, ensuring that candidate risk parameters were grounded in operational practice. Candidate metrics were evaluated against core criteria of physical relevance, operational observability within standard supervisory control and data acquisition architectures, and sensitivity to early-stage system degradation. Although indicators achieving an attention threshold of fifty percent were preliminarily retained, the authors deliberately preserved solar and wind curtailment risks despite lower local survey scores, recognizing that growing renewable penetration inevitably makes energy accommodation capability a critical systemic vulnerability across evolving regional interconnections.
The finalized hierarchical evaluation index system encompasses four primary operational dimensions and ten secondary mathematical formulations designed in dimensionless form to allow unified quantitative comparison. The first primary dimension, distribution network operational security, quantifies node voltage limit violation risks, branch active power limit violation risks, and distribution-side power factor deviations from allowable operational tolerances. The second dimension, transmission network frequency stability, models steady-state frequency limit violations alongside the dynamic frequency transient rate of change, capturing acute system vulnerability during abrupt generation or load imbalances. The third dimension evaluates system supply-demand balance and dispatch flexibility by computing positive reserve shortage risks, negative reserve shortage risks, and transmission-distribution tie-line power fluctuation variances relative to scheduled exchange values. The fourth dimension incorporates renewable energy accommodation capabilities, mathematically formulating the curtailment risks associated with clustered wind turbines and photovoltaic installations when standby-start generator capacities and aggregate system loads diverge from intermittent generation peaks.
Determining the relative importance of these multidimensional indicators requires balancing human engineering heuristics with the empirical statistical properties embedded within operational grid datasets. To achieve this balance, the authors established a dual-track combined weighting mechanism that fuses the subjective Order Relation Analysis method, designated G1, with the objective Criteria Importance Through Intercriteria Correlation method, known as CRITIC. The subjective G1 technique establishes strict order relations among candidate parameters through iterative expert consensus, using linguistic importance ratios between adjacent indicators to derive subjective weight vectors without constructing cumbersome pairwise judgment matrices or executing iterative consistency corrections. Concurrently, the objective CRITIC algorithm processes empirical operational measurements by normalizing raw parameter scores, quantifying contrast intensity through sample standard deviations, and measuring inter-indicator conflict using mathematical correlation coefficients. By setting symmetric balance coefficients of zero point five to combine the subjective and objective weight vectors, the framework synthesizes engineering expertise with objective data structures, preventing individual statistical anomalies or subjective cognitive biases from distorting indicator weight distributions.
To resolve the compounded randomness and fuzzy boundary conditions that characterize power system transitions between safe and hazardous operational states, the framework applies nonlinear cloud model theory. By bridging probability theory and fuzzy set mathematics, cloud models characterize uncertain concepts using three core digital parameters: expectation, entropy, and hyper-entropy. Expectation represents the mathematical center of gravity of qualitative risk semantics, entropy characterizes the dispersion and fuzziness associated with overlapping risk tier boundaries, and hyper-entropy measures the stochastic variability and thickness of entropy itself. Standard risk evaluation intervals spanning from zero to ten are mapped across five distinct operational security tiers, ranging from Level I, indicating safe and stable operation, to Level V, representing severe operational risk. By assigning a calibrated hyper-entropy coefficient of zero point one, validated through extensive Monte Carlo simulations, the researchers established standardized baseline clouds that capture gradual system deterioration without suffering from the rigid, artificial cutoffs enforced by traditional fuzzy membership functions.
The practical assessment sequence employs an inverse cloud generator to convert distributed expert scoring matrices and continuous telemetry inputs into discrete indicator clouds, which are subsequently aggregated using forward cloud algorithms and the unified G1-CRITIC weight vectors. As secondary indicator clouds are synthesized into primary dimensional models and target-layer comprehensive risk clouds, qualitative boundary confusion is resolved through a cloud membership degree formula. Rather than relying on visual inspection of cloud droplet distributions across ambiguous borderline intervals, the authors integrated normal distribution integrals and Euclidean distance parameters to compute precise mathematical similarity coefficients between system operational clouds and the five standardized risk baselines. This numerical formulation yields an exact percentage distribution of cloud membership across every security tier, providing dispatchers with an unambiguous, probabilistic profile of real-time operating margins and localized vulnerability concentrations.
To rigorously examine the performance and adaptability of the proposed methodology, the authors modeled three distinct transmission and distribution network environments in China exhibiting contrasting resource endowments and coupling characteristics. System 1 represented an industrial park configuration in southern China utilizing a modified IEEE 33-bus distribution system linked to a 5-bus transmission equivalent, incorporating rooftop photovoltaics, combined heat and power generation, and battery energy storage where distributed resources met over forty-two percent of peak demand. System 2 modeled an eastern China demand-response pilot based on an IEEE 69-bus distribution architecture with a 3-bus transmission interface, aggregating flexible air-conditioning clusters, electric vehicle charging facilities, and interruptible industrial loads providing substantial demand-side curtailment capacity. System 3 simulated an operational 110-bus distribution network in China connected to an 8-bus transmission equivalent, hosting massive distributed photovoltaic arrays, electric thermal storage installations, and charging stations that pushed renewable penetration to fifty-three point seven percent, generating pronounced midday reverse power flows across the transmission-distribution interface.
Comprehensive numerical calculations across the test cases revealed that distribution network operational security constituted the most influential primary dimension with an overall weight of thirty-one point eleven percent, followed closely by supply-demand balance and dispatch flexibility at twenty-seven point sixty-six percent. Transmission frequency stability and renewable energy accommodation registered weights of twenty-two point twenty-two percent and nineteen point zero two percent, respectively. At the secondary indicator level, positive reserve shortage risk emerged as the single most critical vulnerability, claiming a weight of thirteen point forty-seven percent, followed by frequency transient violation rates at ten point twelve percent and power factor limit violations at nine point zero one percent. These findings confirm that inadequate reserve margins and dynamic frequency volatility represent the primary operational hazards facing coordinated power networks. When evaluated through target-layer cloud membership, Systems 1 and 2 exhibited secure profiles dominated by Level II low-risk memberships of forty-eight point eight percent and forty-nine point seven percent. In contrast, System 3 shifted markedly toward higher hazard tiers, exhibiting a dominant Level III moderate-risk membership of fifty-nine point seven percent, an overall expectation value of two point twenty-six, and the emergence of a three point six percent Level IV high-risk membership driven by severe tie-line power oscillations and insufficient flexible reserves.
The researchers confirmed the methodological reliability and stability of the framework through exhaustive sensitivity assessments, comparative multi-criteria decision-making analyses, and retrospective historical incident validations. Parameter sensitivity sweeps systematically adjusted subjective weight coefficients from zero point one to zero point nine, demonstrating that the relative risk ranking remained invariant across all scenarios, with System 1 consistently exhibiting the lowest risk and System 3 the highest. Cross-validation against classical TOPSIS, Rank Sum Ratio, and VIKOR algorithms reproduced identical system rankings while confirming that the cloud model uniquely provides granular boundary transition and uncertainty data unavailable in conventional decision models. Furthermore, back-testing against three historical operational events in regional Chinese power networks—a midday reverse power flow voltage event, an industrial reserve shortage surge, and a demand-response frequency deviation—demonstrated high quantitative concordance with actual on-site investigation findings, reproducing dominant membership assignments of fifty-eight point seven percent, forty-seven point nine percent, and forty-nine point two percent. Repeated perturbation simulations introducing five percent random noise across normalized inputs showed that the combined G1-CRITIC approach reduced risk expectation volatility by thirty-six to forty-nine percent compared to isolated single-weighting methods, validating the architecture as an exceptionally resilient tool for dispatch optimization and preventive grid control.
Subject of Research: Operational risk assessment of integrated transmission and distribution power systems
Article Title: Subjective–objective hybrid weighting and cloud model for operational risk quantification of integrated transmission–distribution systems
Article References: Pan, L., Yang, X., Yuan, S., Chen, T., & Wei, C. (2026). Subjective–objective hybrid weighting and cloud model for operational risk quantification of integrated transmission–distribution systems. Sustainable Energy Research, 13(1), Article 45. https://doi.org/10.1186/s40807-026-00279-y
Image Credits: AI Generated
DOI: 10.1186/s40807-026-00279-y
Keywords: power system reliability, transmission and distribution networks, operational risk assessment, cloud model theory, G1 method, CRITIC method, hybrid weighting, distributed generation, renewable energy integration, reserve capacity adequacy, rate of change of frequency, voltage limit violations, tie-line power fluctuations, multi-criteria decision making, power grid dispatch
Tags: cloud model theoryCRITIC methodDistributed GenerationG1 methodhybrid weightingmulti-criteria decision-makingoperational risk assessmentpower grid dispatchpower system reliabilityrate of change of frequencyrenewable energy integrationreserve capacity adequacytie-line power fluctuationstransmission and distribution networksvoltage limit violations